Characteristics
Application : high temperature or cooled furnaces , fired on liquid and solid fuels
Detection of the pulsatory light spectrum of the flame to which it is aimed
Not sensitive to ultraviolet rays or non-pulsatory infrareds, or other flames
Intrinsic positive safety (controlled by CETEN APAVE International) with immediate trip off in case of any failure
Easy selection of the cross-over frequencies and simple site adjustment
Detection level : local display (LED) and remote signal (4-20 mA)
Trip-off time < 3 sec
Flame presence : Available on two independent contacts
Temperature of scanner < 60oC
Temperature of control box < 50oC
|